SECTION 5. ROOF AND WALL COVERING
5.1 GENERAL
5.1.1 Wall panels shall be PBR, Vistashadow™, ShadowRib™, or NuWall™ as specified.
5.1.2 Roof Panels shall be PBR, Double-Lok® Machine Seam Standing Seam, Ultra-Dek® Snap Seam Standing Seam, SuperLok™ Standing Seam, or BattenLok® Standing Seam Roof System.
5.1.3 PBR roof and wall panels as specified shall be either 26 gauge steel, coated both sides with an aluminum-zinc alloy or 26 gauge steel, coated with Signature 200 Series siliconized polyester finish or 26 gauge steel, coated with Signature 300 Series (70% fluoropolymer) finish, all with an aluminum-zinc alloy substrate.
5.1.4 Vistashadow™ wall panels as specified shall be 26 gauge steel, coated with a Signature 200 Series siliconized polyester finish or 26 gauge steel, coated with Signature 300 Series (70% fluoropolymer) finish, all with an aluminum-zinc alloy substrate.
5.1.5 ShadowRib® wall panels as specified shall be 24 or 22 gauge steel, available with either a smooth texture or an embossed texture (reduces oil canning) with either a Signature 200 Series siliconized polyester finish or a Signature 300 Series (70% fluoropolymer) finish, all with an aluminum-zinc alloy substrate.
5.1.6 NuWall™ wall panels as specified shall be 26, 24, or 22 gauge steel, available with either a smooth texture or an embossed texture (reduces oil canning) with either a Signature 200 Series siliconized polyester finish or a Signature 300 Series (70% fluoropolymer) finish, all with an aluminum-zinc alloy substrate.
5.1.7 Ultra-Dek® and Double-Lok® Standing Seam Roof System panels as specified shall be either 24 gauge steel coated with an aluminum-zinc alloy, 24 gauge coated with Signature 200 Series siliconized polyester with an aluminum-zinc alloy substrate, or 24 gauge pre-coated with a Signature 300 Series (70% fluoropolymer) finish over an aluminum-zinc alloy substrate.
5.1.8 BattenLok® Standing Seam roof panels as specified shall be either 24 gauge steel coated with an aluminum-zinc alloy or 24 gauge pre-coated with a Signature 300 Series (70% fluoropolymer), finish over an aluminum-zinc alloy substrate.
5.1.9 SuperLok™ Standing Seam roof panels as specified shall be either 24 gauge steel coated with an aluminum-zinc alloy or 24 gauge pre-coated with a Signature 300 Series (70% fluoropolymer) finish over an aluminum-zinc alloy substrate.

5.2 PANEL DESCRIPTIONS
5.2.1 PBR Panel: Panels shall have four (4) major ribs 1 1/4” high, spaced 12” on center. Between the major corrugations are two (2) minor corrugations. All sidelaps shall be composed of one major rib from each adjacent panel utilizing the underlying purlin bearing rib for support. Each panel shall provide 36” net coverage in width.
5.2.2 Vistashadow Wall Panel: Panels shall have four (4) major ribs 1 1/8” high, spaced 12” center. Panel design provides a decorative smooth shadowline with a semi-concealed fastener appearance. All sidelaps shall be composed of one major rib from each adjacent panel. Each wall panel shall provide 36” net coverage in width.
5.2.3 “A” Wall Panel: Panels design provides a decorative smooth shadowline with a semi-concealed fastener appearance. All sidelaps shall be composed of one major rib from each adjacent panel. Each wall panel shall provide 36” net coverage in width.
5.2.4 ShadowRib Wall Panel: Panels shall be 3 inches deep with alternating 5 1/4” wide x 1 1/2” deep fluting ribs. Panel design provides a decorative, concealed fastener, smooth or embossed panel surface. All sidelaps shall be composed of 3” deep, concealed fastener ribs. Each wall panel shall provide a net coverage of 16”.
5.2.5 NuWall Wall Panel: Panels shall be 2 1/2” deep with alternating 1/2” fluting ribs. Panel design provides a decorative, concealed fastener, smooth or embossed panel surface. All sidelaps shall be 2 1/2” deep, concealed fastener ribs. Each panel shall provide a net coverage of 12”
5.2.6 Double-Lok® Machine Seam Roofing System: Panels shall UL90 rated, rollformed, 24 gauge (minimum) structural quality aluminum-zinc alloy coated steel sheet complying with ASTM A792. All aluminum-zinc alloy steel sheeting shall have a minimum of class AZ-50 coating on both sides and a minimum yield of 50,000 psi. Panels shall have a new coverage of 24” with a 3” high rib at both sidelaps. The panels are to be mechanically seamed together at the sidelaps utilizing the Pittsburgh Seam. Endlaps shall be pre-punched for proper placement of fasteners. Panels shall be attached to the structural system with concealed clips with factory applied mastic.
5.2.6.1 Low Floating Clips: The clips shall be 3 3/8” in height providing a 3/8” clearance for insulation between the panel and the purlin. Floating clips shall provide a minimum of 2” movement to allow for expansion and contraction.
5.2.6.2 High Floating Clips: The clips shall be 4 3/8” in height providing a 1” thermal spacer for added insulation at the purlins. Floating clips shall provide a minimum a 2” movement to allow for expansion and contraction.
5.2.7 Ultra-Dek® Snap Seam Roofing System: Panels shall be UL90 rated rollformed, 24 gauge (minimum) structural quality aluminum-zinc alloy coated steel sheet complying with ASTM A792. Aluminum-zinc alloy sheet steel shall have a minimum of class AZ-50 coating on both sides and a minimum yield stress of 50,000 psi. Panels shall have a net coverage of 24” and a 3” high rib at both sidelaps. One side of the panel shall be female in configuration, suitable to accept the other male side, and form a locking assembly. Panel sidelaps shall have factory applied foamable hot melt mastic sealant. Endlaps shall be pre-punched for proper placement of fasteners. Panels shall attach to the structural system with concealed clips that have factory-applied mastic and be designed so that movement between the panel and clip does not occur.
5.2.7.1 Utility Clips: The clips shall be 3” in height and used when insulation is not required.
5.2.7.2 Low Fixed Clips: The clips shall be 3 3/8” in height providing a 3/8” clearance for insulation between the panel and the purlin.
5.2.7.3 High Fixed Clips: The clips shall be 3 3/8” in height to accommodate a 1” thermal spacer for added insulation at the purlins.
5.2.7.4 Low Floating Clips: The clips shall be 3 3/8” in height. Floating clips shall provide a minimum of 2” movement for expansion and contraction while allowing 3/8” clearance for insulation between the panel and the purlins.
5.2.7.5 High Floating Clips: The clips shall be 4 3/8” in height. Floating clips shall provide a minimum of 2” movement for expansion and contraction while allowing a 1” thermal spacer for added insulation at the purlins.
5.2.8 BattenLok® Standing Seam Roofing System: Panels shall be UL90 rated rollformed, 24 gauge (minimum) structural quality aluminum-zinc alloy coated steel sheet complying with ASTM A792. The aluminum-zinc alloy sheet shall have a minimum of class AZ-50 coating on both sides and a minimum yield stress for 50,000 psi. Panels shall have a net coverage of 16” and a 2” high rib at both sidelaps. The panels are joined at the edges with a mechanically locked standing seam. Panel sidelaps shall have a factory-applied mastic and be designed so that movements between the panel and clip does not occur.
5.2.8.1 Utility Clips: The clips be 2” in height and used when insulation is not required.
5.2.8.2 Low Fixed Clips: The clips shall be 2 3/8” in height providing a 3/8” clearance for insulation between the panel and the purlin.
5.2.8.3 High Fixed Clips: The clips shall be 3 3/8” in height to accommodate a 1” thermal spacer for added insulation to the purlins.
5.2.8.4 Low Floating Clips: The clips shall be 2 3/8” in height. Floating clips shall provide a minimum of 1 5/8” movement for expansion and contraction.
5.2.8.5 High Floating Clips: The clips shall be 3 3/8” in height. Floating clips shall provide a minimum of 1 5/8” movement for expansion and contraction.
5.2.9 SuperLok Standing Seam Roofing System: Panels shall be UL90 rated rollformed, 24 or 22 gauge structural quality aluminum-zinc alloy coated steel complying with ASTM A792. The aluminum-zinc steel shall have a minimum of class AZ-50 coating on both sides and a minimum yield stress for 50,000 psi. Panels shall have a net coverage of either 12 or 16 inches and a 2” high rib at both sidelaps. Panels sidelaps shall have a factory-applied hot melt mastic and are designed for electrically powered mechanical attachment to the structure utilizing concealed clips.
5.2.9.1 Utility Clips: The clips shall be 2” in height and used when insulation is not required.
5.2.9.2 Low Fixed Clips: The clips shall be 2 3/8” in height, providing a 3/8” clearance for insulation between the panel to the purlins.
5.2.9.3 High Fixed Clips: The clips shall be 3 3/8” in height to accommodate a 1” thermal spacer for added insulation to the purlins.
5.2.9.4 Low Floating Clips: The clips shall be 2 3/8” in height. Floating clips shall provide a minimum of 1 5/8” movement for thermal expansion and contraction as well as 3/8” clearance for insulation between the panel and purlin.
5.2.9.5 High Floating Clips: The clips shall be 3 3/8” in height. Floating clips shall provide a minimum of 1 5/8” movement for thermal expansion and contraction as well as the height to accommodate a 1” thermal spacer for added insulation to the purlins.

(continued on page 4)