EWP Panel Test Data
Test
|
Purpose |
Procedure |
Results |
|
Thermal Resistance |
Determines insulating properties of the panels |
ASTM C 236 |
Good R values for an HCFC Foam
System |
|
Air Leakage |
Measures air leakage through the panel joints |
ASTM E 283 |
The leakage rate for panel will not exceed 0.01 CFM/SF at 40 psf pressure differential |
|
Water Penetration |
Measures water leakage through the panel joints |
ASTM E 331 |
No water penetration at pressure differential of 50 psf |
|
Strength |
Determines the load/span
properties of the roof and wall |
ASTM E 72 |
Panel load/span and deflection tables are available |
|
Ignition Properties |
Determines ignition temperatures of the panel core material |
ASTM D 1929 |
Self-ignition temperature is 860
degrees F. |
|
Surface Burning |
Determines the surface burning characteristics of the core and panels |
Underwriters |
Core Material (5") Finished Panel |
|
Southwest |
Finished
Panel |
||
|
Room Fire Test |
Evaluates the burning of roof and wall panels in a room configuration |
Factory Mutual |
Panel is rated Class 1 to 30 ft. high, 5 in. max thickness |
Note: The numerical flame spread rating is not intended to reflect hazards
presented by this or any other material under actual fire conditions.
EWP Panel Thermal Properties
|
Product Code |
Thickness |
"U" Factor |
"R" Factor |
|
EWP 200 |
2" |
.072 |
13.9 |
|
EWP 250 |
2 1/2" |
.058 |
17.3 |
|
EWP 300 |
3" |
.048 |
20.8 |
|
EWP 400 |
4" |
.036 |
27.7 |
|
EWP 500 |
5" |
.029 |
34.6 |
Note: Insulation
values determined by tests conducted in accordance with ASTM C 236 at a mean
temperature
of 75
degrees F., winter condition corrected to 15 mph outside and still inside.